Design of a comprehensive protection algorithm for fault detection, classification, and location in high voltage direct current transmission lines connected to wind farms based on local terminal measurements
With the increasing adoption of bipolar high-voltage direct-current (HVDC) transmission lines for wind farm integration, the development of fast, accurate, and communication-independent protection schemes has become a critical technical requirement. This paper proposes a comprehensive protection algorithm within an integrated single-ended framework that performs fault detection, fault classification, and fault location simultaneously using only local voltage and current measurements. In the detection stage, transient current signals are processed through common- and differential-mode decomposition to ensure fast and reliable fault inception identification. In the classification stage, the faulted pole and fault type are determined by exploiting the dynamic voltage patterns of the two poles. For fault location, an analytical model is developed based on the voltage–current relationships of the bipolar HVDC line, while explicitly accounting for self-resistance, mutual resistance, and inter-pole coupling effects. In addition, the protection thresholds are systematically defined using per-unit parameters and dimensionless indices, together with statistical criteria extracted from the system behavior under both normal and faulted conditions; this enhances their tunability, robustness, and applicability across different HVDC configurations. The proposed method is evaluated in the MATLAB/Simulink environment under varying operating conditions, fault resistance values, and line-parameter uncertainties. Simulation results show that the average and maximum fault detection delays are 3.32 ms and 4.96 ms, respectively. Moreover, the faulted pole is identified with complete accuracy, while the average and maximum fault-location errors are 0.69% and 0.98%, respectively, confirming the high speed, accuracy, and robustness of the proposed protection scheme.
In recent years, high penetrations of inverter-based resources are posing significant challenges to the medium-voltage networks, in which protection schemes based on high fault currents and unidirectional power flow may not perform as expected. This paper proposes a dynamic fault-detection and relay-coordination scheme...
Muhammad Abdul Rauf, Munira Batool, I. Madni· Energies· 0 citations
The study of hybrid multiterminal high-voltage direct current (HVDC) systems revealed different outcomes regarding their performance under fault conditions. Previous research showed that under the fault conditions, the high-voltage direct current (HVDC) voltage experienced a drop to zero, accompanied by a reverse overs...
Olumoroti Ikotun, E. Ojo, M. Kabeya· Symmetry· 0 citations
DC distribution networks employing a low-current grounding method offer high power supply reliability. However, when a single-pole grounding fault occurs on a feeder, the fault current characteristics are not distinct, making accurate fault identification and feeder protection challenging. Prolonged operation with the...
Wei Jin, Rui-Ya Zhang, Zi-Jie Hu et al.· Energies· 0 citations
The rapid expansion of voltage source converter-based high voltage DC grids has made DC fault protection a critical research priority, due to low network impedance and the absence of natural current zero crossings. DC fault current limiters have emerged as an effective means of suppressing the rapid rise of fault curre...
Mohammad Soltani Mohammadi, Saeed Norouztamar, Hossein Iman-Eini et al.· IEEE Open Journal of Power E...· 0 citations
An integrated approach that combines a resistive superconducting fault current limiter (RSFCL) with an artificial neural network (ANN)-based intelligent fault diagnosis framework provides an effective and intelligent solution for fault diagnosis and protection in DG-integrated power systems.
L. R. Chandran, Ilango Karuppasamy, M. Nair· International Journal of App...· 0 citations
The increasing penetration of inverter-based renewable energy resources is reshaping transmission-line fault characteristics and weakening protection criteria designed for synchronous-generator-dominated grids. This paper proposes an internal-fault identification scheme based on voltage–current coupling characteristic...
Long-Fei Ren, Xiao He, Wei-Zhen Li et al.· Electronics· 0 citations