Skip to content
Conference

Distance Protection Method for AC Transmission Lines Considering VSC Impact

Aug 2026 · 2026 6th International Conference on Mechanical, Electronics and Electrical and Automation Control (METMS) · pp. 288-291 · 0 citations · 12 references

Abstract

The integration of Voltage Source Converter (VSC) based flexible DC systems leads to the maloperation of traditional distance protection, threatening grid stability. This paper reveals how converter current-limiting and decoupling controls cause fault current phase shifts under phase-to-phase faults, forcing the operating angle to migrate and triggering protection maloperation. An adaptive distance protection method integrating transient information is proposed. A fast directional element utilizes initial transient components before control interference to achieve ultra-fast directional discrimination. An adaptive adjustment angle dynamically modifies the impedance operating boundary. PSCAD simulations verify that this method mitigates VSC controlled-source interference, demonstrating performance and adaptability.

View source