2026· IEEE Open Access Journal of Power and Energy· Vol 13, pp. 892-903· 0 citations· 29 references
Abstract
Converter-dominated microgrids (MGs), an emerging class of converter-dominated power systems (CDPS), feature extensive converter-interfaced distributed energy resources (DERs) and power-electronic loads such as variable-frequency drives (VFDs). A representative example is the Natural Energy Laboratory of Hawaii Authority (NELHA) MG located in Hawaii, which exhibits converter-dominated behavior due to extensive power-electronic interfacing and large motor-drive loads. In particular, its VFD-driven pump systems draw non-sinusoidal currents that cause notable harmonics at the point of common coupling (PCC), motivating a unified approach that combines harmonic mitigation with fast primary frequency support. This paper proposes a multifunctional battery energy storage system (BESS) control strategy that performs shunt active power filtering and droop-based primary frequency control within a single converter. The proposed controller integrates shunt active power filter (SAPF) harmonic-current reference generation into the BESS droop loop, enabling the BESS grid-side converter to inject both the active power required for frequency support and the compensation currents required to cancel load harmonics at the PCC. By leveraging the existing BESS inverter and DC-link, the approach avoids a separate dedicated SAPF inverter and DC-link capacitor, reducing additional hardware and semiconductor utilization. Hardware-in-the-loop (HIL) tests of a NELHA-inspired microgrid model validate the effectiveness of the proposed control strategy, demonstrating harmonic mitigation together with stable frequency response and power sharing under nonlinear-load conditions. Furthermore, an FFT-based analysis of the proposed HIL case yields a grid-current THD of 0.92%. For comparative context, this result is evaluated against literature-reported THD values of 1.18% for a conventional hysteresis-controlled SAPF and 5.88% for an existing fixed-switching-frequency active harmonic-filtering method. The proposed system also provides integrated droop-based primary frequency support.
As renewable energy sources and nonlinear loads are integrated into microgrids supplying isolated loads, they are becoming increasingly dynamic and challenging to operate. Power quality and stability of isolated microgrids may be adversely affected by nonlinear loads, which introduce reactive power demand, harmonic dis...
Bisma Hamid, Ikhlaq Hussain· Proceedings of the Instituti...· 0 citations
This paper proposes a modeling, simulation, and operational analysis framework for the conversion of an electrical distribution network into a microgrid (MG) integrating renewable energy sources, battery energy storage, and green hydrogen technologies. The proposed framework targets enhanced operational resilience and...
Camila M. Galo Da Silva, José F. C. Castro, D. P. Barbosa et al.· IEEE Access· 0 citations
In battery energy storage systems (BESSs) in microgrids, traditional proportional–integral (PI) controllers remain a popular choice for management. The PI-based system often fails during sharp transients and under sudden shifts in solar irradiance or load demands. PI-based systems typically exhibit sluggish recovery ti...
Haider H. Ali, Basil H. Jasim, A. Alqurashi et al.· Engineer· 0 citations
The increasing integration of renewable energy sources (RESs), battery energy storage systems (BESSs), and electric vehicle (EV) charging infrastructure into modern power systems has introduced significant challenges, including power-quality degradation, poor voltage regulation, harmonic distortion, and complex dynamic...
S. Begum, Ujwala Gajula, P. R. Reddy et al.· International Journal of Adv...· 0 citations
This paper presents a comprehensive analysis and design of an enhanced control framework for offshore wind turbine generators (WTGs) equipped with permanent-magnet synchronous generators (PMSGs) and full-scale power converters. The proposed strategy integrates Model Predictive Control (MPC) for maximum power point trac...
K. A. Baizhanov, S. Issenov· IOP Conference Series: Earth...· 0 citations
Grid-connected power electronic converters are highly sensitive to disturbances such as DC offset, frequency deviations, and voltage harmonics, which may degrade current control accuracy and overall power quality. This article presents an advanced control strategy for a single-phase five-level H-bridge inverter integra...
S. Khalil, Ahmed Abbou, Naima Oumidou et al.· Electrica· 0 citations