Energy-State PI Control with a Linear Disturbance Observer for DFIG DC-Link Regulation During LVRT
Abstract
To address dc-link energy accumulation and delayed voltage-PI response during balanced DFIG voltage sags, this paper proposes an energy-state proportional-integral controller with a two-state linear disturbance observer (EPI-LDO). Capacitor energy serves as the outer-loop state and directly represents the accumulated mismatch between rotor-side input power and grid-side converter (GSC) output power. The observer reconstructs an aggregate disturbance containing rotor-side dc power, converter losses, and unmodeled terms, and converts this estimate into a feedforward d-axis active-current reference. An independent q-axis branch supplies reactive current, while a q-priority allocator preserves the reactive-current request when the configured current limit becomes active. Matched simulations evaluate EPI-LDO against conventional voltage PI and energy PI under balanced sags with 0.30 and 0.50 pu retained PCC voltage at three operating points and under parameter perturbations, measurement noise, sensor and control delays, and forced current-limiting conditions. Across all matched operating points, EPI-LDO produces smaller dc-link voltage excursions than both baselines. Under the specified noise and delay conditions, observer tracking remains bounded, and the d/q-axis current allocation remains within the configured limit.