FEATURES OF CONSTRUCTION OF MULTI-STAGE ZERO-SEQUENCE CURRENT PROTECTION IN 35 KV NETWORKS OF METALLURGICAL PRODUCTION
Abstract
This article examines the design of a multi-stage zero-sequence current protection system for 35 kV distribution networks of metallurgical plants, particularly converter shops. The article examines the fundamental principles of selective protection against single-phase ground faults using the 3I0 current and 3U0 voltage signals. Using a real-world 35 GPP-19 switchgear circuit as an example, approaches to selecting tripping settings and time delays for various protection stages are analyzed. The choice of resistive neutral grounding with a low-impedance resistor integrated into the arc suppression device is substantiated as the most suitable technical solution for 35 kV networks of metallurgical production. Based on the calculation of capacitive earth fault currents performed for cable connections of ladle furnace units, filter compensating devices and arc suppression devices, a four-stage protection structure is proposed, including an instantaneous stage for connections with zero-sequence current transformers, stages with delays of 0.3 s, 0.6 s and a reserve stage of 0.9 s for disconnecting the input of the busbar section.