Assessment and Improvement Strategies for the Winter Indoor Thermal Environment of Temporary Construction-Site Buildings in Cold Regions
Abstract
Temporary construction-site buildings in cold regions often suffer from poor indoor thermal environments and high heating energy consumption, while field-based studies and cost-effective improvement strategies remain limited. This study investigated typical office and dormitory temporary buildings in Yan’an, China, using 48-h winter field measurements and 50 thermal comfort questionnaires to identify indoor thermal environment problems, followed by a calibrated and validated EnergyPlus model. The results showed that the average indoor air temperature was only 3.6 °C under unheated conditions, with envelope interior surface temperatures below 5 °C. Under air-conditioning heating, the average indoor temperature increased to 15.3 °C but remained below the basic winter requirement. Office and dormitory buildings showed different heating demand patterns, supporting differentiated heating schedules. Compared with 24-h continuous heating, the recommended intermittent scenarios reduced heating load by 888.10 and 119.42 kWh, respectively; compared with baseline operation, reductions were 13.2% and 5.7%. Window and envelope improvements reduced heating load with diminishing marginal benefits. A 12-mm air layer was recommended for thermally broken aluminum double glazing, with rock wool thicknesses of 105 mm, 100 mm, and 95 mm for walls, roof, and floor, respectively, reducing heating load by 13.68% and 20.48% for office and dormitory buildings.