Exergetic assessment of marine heat pump units with a low-grade heat source: seawater

Sep 2026 · Труды Санкт-Петербургского государственного морского технического университета · 0 citations · 2 references

Abstract

Background

Decarbonization of maritime transport requires the integration of renewable energy sources into ship power systems. Seawater is an inexhaustible low-grade heat source, but its efficient use by heat pumps with different refrigerants under marine conditions has been understudied.

Aim

To perform a comparative energy and exergy analysis of seawater-to-water vapor compression heat pumps using R134a, R407C, and R717 (ammonia) with seawater as a renewable source for the Baltic, North, and Arctic waters, and to develop recommendations for refrigerant selection.

Methods

Parametric calculations were carried out for source temperatures from –1.5 °C (seawater under ice cover) to 10 °C (summer), at a condensation temperature of 50°C and a heat output of 100 kW. Energy (coefficient of performance, COP) and exergy methods with loss localization in the compressor, condenser, expansion valve, and evaporator were applied. Marine factors (corrosion activity, vibration, space and weight constraints) were taken into account.

Results

Ammonia (R717) showed the best performance: COP = 5.91, exergy efficiency ηex = 0.331, and minimum mass (0.008 kg/s) and volumetric (0.00158 m³/s) flow rates. When the source temperature decreased to –1.5 °C, the COP of R717 was 3.85, which is higher than the summer values of R134a. Exergy losses for R717 are maximum in the condenser (41.4%), while for R134a and R407C they are maximum in the compressor (45.6% and 38.2%, respectively).

Conclusions

A comparative exergy analysis of marine heat pumps with a renewable source (seawater) has been performed for a wide range of source temperatures, including negative values (down to –1.5 °C), with a justification for the non-freezing behavior of saline water. It was established that ammonia (R717) is the thermodynamically most efficient refrigerant: COP = 5.91, ηex = 0.331 at T1 = 10 °C; even at –1.5 °C, COP = 3.85, which enables the use of such heat pumps in Arctic conditions. Based on the exergy loss analysis, priority optimization directions have been identified: for R717, highly efficient compact condensers; for R134a/R407C, reliable compressors with high efficiency and electronic expansion valves. The use of seawater heat as a renewable energy source makes it possible to replace 30%–40% of the ship's heat load, thereby reducing fuel consumption and CO₂ emissions.