Skip to content
Open access

Line Current Harmonic Elimination under Nonlinear Loads Using Voltage Reference Configuration (VRC) Control Algorithm of PV-DSTATCOM for Distribution Network

Unknown authors
Oct 2026 · International Journal of Science and Applied Information Technology · 0 citations

Abstract

Proliferation of nonlinear electronic loads have injected harmonics into the distribution network and polluted the supply network with power quality problems. The three- phase three-wire PV-DSTATCOM with VRC control algorithm in this study is capable suppress harmonic currents under nonlinear loads and improve the power quality at the PCC. Thus, the proposed PV-DSTATCOM will improve the PCC line currents to be sinusoidal, low current harmonic according to IEEE Standard 519-2014 and in-phase with the line voltage. The DSTATCOM performance is validated by using MATLAB software. The optimum design of PV array with DC-DC boost converter is evaluated in term of techno- economic aspects with Homer Pro software. FPGA-in-the- loop (FIL) testing of the proposed control algorithm has been done prior to hardware implementation to verify its effectiveness. The performance of a DSTATCOM prototype is then studied under steady-state and dynamic scenarios using an Altera FPGA Cyclone IV EP4CE115F29C7N FPGA board.

Read PDF