Cyber Resilient Grid Forming Smart Load Control Under False Data Injection and Denial of Service Attacks
Abstract
With increased penetration of grid-forming converter-based renewable energy generation, battery storage and power-electronic-interfaced controllable loads, the power network has become prone to cyber attacks. This paper develops a cyber-resilient control framework for grid-forming smart loads (GFSLs). A system-level small-signal state-space model with the plant’s active and reactive open-loop gains has been extended to include the false data injection (FDI) and denial-of-service (DoS) attack channels. A steady-state analysis further quantifies how corrupted data displaces the operating point and misleads the inertia and voltage loops. As a remedy, an observer-based residual generator with a calibrated $\chi ^{2}$ /CUSUM test is proposed to detect the attacks, and the conditions under which a stealthy attack can evade detection are characterized through left invertibility. Secure state reconstruction, reference saturation, and DoS-aware switching achieve the desired resilience, which is verified through input-to-state stability under bounded FDI and an average-dwell-time condition guaranteeing stability under intermittent DoS. Numerical studies validate the impact prediction, detection performance (delay, receiver operating characteristic, and false-alarm calibration), the single versus multi-sensor stealth contrast, the ISS bound envelope, and a coordinated two-node attack, confirming that the scheme bounds and rejects single-sensor manipulation that the unprotected GFSL cannot withstand.