TL;DR
This paper audits twelve line VSIs on the IEEE 14bus system using continuation power flow (CPF) over 30 scenarios, finding the most reliable index, NVSI, is the most reliable and supplies a severity label, while a consensus vote across all twelve indices supplies a critical-line label.
Abstract
Voltage stability indices (VSIs) are widely used to flag the transmission line most likely to trigger voltage collapse, yet published indices are usually validated at a handful of loading snapshots along a single trajectory. This paper audits twelve line VSIs on the IEEE 14bus system using continuation power flow (CPF) over 30 scenarios (a base case, 19 successful single-line outages and 10 randomized loading directions), each traced to its collapse point and yielding 31,660 line-step samples. Indices are scored on saturation, trend correlation with the loading factor, and single-line bias. We show analytically, and verify on 30,693 in-service samples, that three pairs of published formulas (BVSI/Lp, Lij/Lmn and VQILine/FVSI) are identical, and that the R-multiplied pair BVSI/Lp is structurally blind to the five zero-resistance transformer branches, including the heavily loaded branch 5–6. The Novel Voltage Stability Index (NVSI) is the most reliable index (trend correlation 0.99, 0.4% saturation) and supplies a severity label, while a consensus vote across all twelve indices supplies a critical-line label. A Gradient Boosting classifier trained on 14 raw electrical measurements, with no index as input, reaches F1 = 0.824, recall 0.901 and ROCAUC 0.987 on scenario-disjoint test data, and a Random Forest regressor reproduces NVSI with R^{2} = 0.999. We also observe that the weakest line migrates with loading (5–6, 7–8, 2–3, then 5–6 again in the base case) and that residual errors arise almost entirely among the lines that trade the critical label. A Streamlit application serves both models.
The results demonstrate the potential of the RF–RC model for accurate voltage-magnitude estimation in standard transmission systems, however, the proposed model is dependency-aware rather than topology-aware, and its scalability has been evaluated only on standard IEEE test systems.
Z. Almajali· International Journal of Adv...· 0 citations
The secure operation of a hybrid AC/DC grid requires not only a stable/unstable decision but also the voltage recovery margins of vulnerable buses. This paper presents a cascaded dual-criterion assessment and severity warning framework using a 0.75 p.u./1 s low-voltage-duration check and a 0.8 p.u./10 s recovery check....
Yong Wang, Yu-Xin Dai, Bing-Chen Li et al.· Machines· 0 citations
Rapid identification of static voltage weak buses in large-scale power grids is hindered by the computational burden of bus-by-bus continuation power flow (CPF) verification. This study proposes a GATv2–Jumping Knowledge (GATv2-JK) framework that screens operating conditions by system voltage stability margin and uses...
Zhen-Cheng Liang, Si-Ying Wang, Jun-Hui Liu et al.· Energies· 0 citations
Live-line crossing platforms are exposed to coupled wind, operational, and impact loads while electrical clearance must be maintained. This paper presents a multi-scale LSTM-Transformer for forecasting the continuous overturning stability margin of an insulated telescopic-boom platform at 5s and 30s horizons. Because f...
Li Gong, Jiu-Qi Wang, Wen-Zhe Liu et al.· Advanced Manufacturing Techn...· 0 citations
Faults occurring during power swings, and the evolution of a swing into an unstable condition, cause distance-relay maloperation and cascaded outages. This paper identifies faults, faults during power swings, and power swings, and distinguishes stable from unstable swings in a 9-bus WSCC system modeled in PSCAD/EMTDC....