Numerical Simulation of Flow and Heat Transfer Characteristics of Staggered Circular Finned-Tube Air-Cooled Heat Exchanger
Abstract
The removal of decay heat is essential for safety in nuclear power plants, with the Passive Residual Heat Removal System (PRS) serving as a key design feature. The adoption of natural-draft air-cooled heat exchangers provides sustained heat removal without a specified time limit; in these systems, the air-side thermal resistance dominates the overall heat transfer process. However, the lack of applicable empirical correlations presents a significant challenge to the design of the PRS. In this study, a numerical simulation was carried out to investigate the air-side flow and heat transfer characteristics in finned-tube bundles. The effects of key parameters, including tube arrangement, air velocity, and inclination angle, were analyzed. The results indicated that the staggered arrangement achieved a higher heat transfer coefficient than the aligned arrangement, but at the cost of a higher pressure drop. Within the investigated micro-inclination range of 0° to 5°, tube inclination exerts a negligible influence on both the air-side heat transfer coefficient and pressure drop. New correlations for the heat transfer coefficient and pressure drop were developed for staggered circular finned-tube bundles, providing reliable tools for the design of the PRS in pressurized water reactors.