IGCT Clamp Circuit Impacts on Resonant Operating Principles in Direct Current Transformer
Abstract
The integrated gate-commutated thyristor (IGCT) devices, as widely utilized power semiconductors in hard-switching high-power applications, necessitate an external clamp circuit to limit current slew rate during turn-ON events. While the design and operating principles of the clamp circuit are exhaustively investigated for the hard-switching converters, the inclusion of this circuit in resonant soft-switching converters, such as resonant direct current transformer (DCT), reveals different working principles and impacts due to the sinusoidal current waveforms in the resonant conversion. This paper presents the analysis of the clamp circuit in a CLLC resonant-based DCT with three-level neutral-point clamped (3L-NPC) power stages and presents the impacts on the overall performance and operation followed by good design practices. An experimental validation and characterization are performed on a 5 k V / 5 k V megawatt-scale resonant DCT.