Skip to content
Open access

Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch

Aug 2026 · Energies · 0 citations · 22 references

Abstract

Data centers can provide demand-side flexibility by coordinating computing workloads, cooling systems, and on-site energy resources. However, facility demand varies with information technology (IT) load and cooling operation, making a fixed power usage effectiveness (PUE) or a forecast independent of planned controls inconsistent with dispatch. This paper proposes a control-aware, multi-horizon PUE forecasting framework for coordinated data center demand-side management (DSM) and microgrid dispatch. The key idea of this control-aware approach is to forecast PUE using planned workload and cooling schedules as inputs. A power-consistent Temporal Fusion Transformer (PC-TFT) predicts quantiles of non-IT overhead power and rack inlet temperature from telemetry, weather forecasts, admitted requests, and candidate workload and cooling schedules. Facility power and PUE are derived from the algebraic power balance, ensuring consistency among IT, overhead, and facility power and PUE values no lower than 1. Empirical split conformal calibration and temporally dependent scenarios characterize forecast uncertainty. A trajectory-conditioned piecewise-affine control response map with a recursive thermal state links the forecasts to a risk-informed model predictive controller that coordinates workloads, cooling, photovoltaic generation, battery storage, and grid exchange. The proposed framework is validated through EnergyPlus simulations of a Shenzhen data center, coupled with workload and microgrid simulations. Forecasting performance is compared with persistence and matched-input neural baselines, while dispatch is benchmarked against deterministic and oracle controllers. The results demonstrate improved multi-horizon PUE forecasting accuracy and empirical interval calibration, lower operating cost and peak grid demand, higher renewable energy utilization, and fewer service quality violations. These findings indicate that control-aware, power-balance-constrained probabilistic PUE forecasts can provide a reliable basis for coordinated data center DSM and microgrid dispatch.

Read PDF

Similar papers

Conference Aug 2026

A coordinated dispatch strategy for fluctuation mitigation in data centers considering flexible computing load

Simulation results indicate that the proposed coordinated optimization strategy for data center microgrids can effectively shift peak loads, significantly reduce the curtailment rate of photovoltaic power, and demonstrate good economic performance.

Yucheng Zheng, G. Rashed, Xin-Fa Jiang et al. · 0 citations
Conference Aug 2026

Reliability-Oriented Scheduling for Electricity–Computing Coordination in Data Centers with Adjustable Computing Workloads

Data centers can provide demand-side flexibility by shifting adjustable computing workloads, but price-aware scheduling must preserve service completion and control delay loss. This paper proposes reliability-oriented electricity-computing coordination for data centers. Under a seven-day minute-level setting, an FCFS-l...

Hong-Da Gao, Bao-Di Han · 0 citations
Preprint Aug 2026

Real-Time Control of Sustainable Data Centers: A Two-Layer Model Predictive Control Framework with Workload Flexibility and Heat Recovery

This paper proposes a two-layer model predictive control (MPC) framework for the real-time operation of data centers integrated with on-site photovoltaic generation, battery energy storage, waste heat recovery, and district heating. The upper layer employs scenario-based stochastic optimization to jointly optimize intr...

Wen-Yu Liu, Enea Figini, Mario Paolone · 0 citations
Open access 2026

Risk-Aware Multi-Timescale Scheduling and Distributed Event-Triggered Control for Overload Mitigation in PV-Rich Distribution Networks

: High-penetration distributed photovoltaic (PV) integration improves renewable utilization in distribution networks, but abnormal PV ramps may also be transformed into feeder active-power overloads when coupled with load variation and feeder power-flow baselines. To address this issue, this paper proposes a risk-aware...

Guang-Yuan Xu, Wei Wang, Biao Shi et al. · 0 citations
Conference Aug 2026

Mixed-Criticality, Carbon-Aware Task Scheduling for Smart-Grid Edge-Cloud Computing: A Simulation-Based Heuristic

Smart-grid edge-cloud networks host computational workloads of sharply different operational criticality, from millisecond-sensitive protection and control functions to delay-tolerant analytics and forecasting. Existing scheduling approaches address this heterogeneity only partially: dual-priority service differentiati...

Albashir Bashir, A. Qureshi, Mohd Fareq Abd Malek · 0 citations